MI 3394 CE MultiTesterXA
Instrument set and accessories
5
Only a skilled person familiar with hazardous voltages can perform this
measurement!
DO NOT perform this test if any damage or abnormality (test leads, instrument) is
noted!
Never touch exposed probe tip, connections equipment under test or any other
energized part during the measurements. Make sure that NOBODY can contact them
either!
DO NOT touch any part of test probe in front of the barrier (keep your fingers behind
the finger guards on the probe) – possible danger of electric shock!
It is a good practice to use lowest possible trip-out current.
1.1.2.2
Diff. Leakage, Ipe Leakage, Touch Leakage, Power, Leak’s & Power
It is advisable not to run tested devices with load currents above 10 A for more than
15 minutes. Load currents higher than 10 A can result in high temperatures of On/Off
switch and fuse holders!
1.1.3
Markings on the instrument
Read the Instruction manual with special care to safety operation«. The
symbol requires an action!
Dangerous high voltage is present on terminals during the test. Consider
all precautions in order to avoid risk of electric shock.
Mark on your equipment certifies that it meets European Union
requirements for EMC, LVD, and ROHS regulations.
This equipment should be recycled as electronic waste.
.