4.3.4 Strapping Table
The strapping table is a 2-point to 21-point table used by the
Universal IV to define the relationship between level and
output current. There are five strapping tables built into
the transmitter software. These are: Linear (vertical tank);
Horizontal Tank with flat ends; Horizontal Tank with dished
ends; Horizontal Tank with hemispherical ends; and Spherical
Tank. These predefined tables are automatically created
by selections made with Vessel Config assignment during
Configuration procedure in Section 4.3.
If output-to-level relationship is not defined by one of these
tables, you may create a table in Strapping Table program. To
create a non-linear relationship, you will need at least 3 points
and may use as many as 21 points. A 21-point table will define
relationship to approximately a 0.1% accuracy. Common example
for a simple table would be Cone Bottom Vertical tank which
would require 3 points—bottom, straight-side target point, and
top. However, a more complex geometry could benefit from using
all 21 available points.
• Plan your table by filling out the form below. You may
use first column which lists every 5% between 0 and
100%, or you may fill in your own values in column 2.
• Fill out column 3 with output values corresponding to
those listed in column 1 or 2.
Summary of Contents for DREXELBROOK Universal IV Lite
Page 4: ...This page has no content...
Page 56: ...Section 4...
Page 67: ...Troubleshooting 61 Table 5 1 Problem Symptom Chart...
Page 78: ......
Page 80: ......
Page 85: ...Control Drawings 79 8 1 ATEX IECEX Section 8 Control Drawings...
Page 86: ...Universal IV Installation and Operating Instructions 80 8 1 ATEX IECEX Continued...
Page 87: ...Control Drawings 81 8 1 ATEX IECEX Continued...
Page 88: ...Universal IV Installation and Operating Instructions 82 8 1 ATEX IECEX Continued...
Page 89: ...Control Drawings 83 8 1 ATEX IECEX Continued...
Page 90: ...Universal IV Installation and Operating Instructions 84 8 1 ATEX IECEX Continued...
Page 91: ...Control Drawings 85 8 1 ATEX IECEX Continued...
Page 92: ...Universal IV Installation and Operating Instructions 86 8 1 ATEX IECEX Continued...
Page 93: ...Control Drawings 87 8 2 FM US FMC...
Page 94: ...Universal IV Installation and Operating Instructions 88 8 2 FM US FMC Continued...
Page 95: ...Control Drawings 89 8 2 FM US FMC Continued...
Page 96: ...Universal IV Installation and Operating Instructions 90 8 2 FM US FMC Continued...
Page 97: ...Control Drawings 91 8 2 FM US FMC Continued...
Page 98: ...Universal IV Installation and Operating Instructions 92 8 2 FM US FMC Continued...
Page 99: ...Control Drawings 93 8 2 FM US FMC Continued...
Page 100: ...Universal IV Installation and Operating Instructions 94 8 2 FM US FMC Continued...
Page 101: ...Control Drawings 95 8 2 FM US FMC Continued...
Page 102: ...Universal IV Installation and Operating Instructions 96 8 2 FM US FMC Continued...
Page 103: ...Control Drawings 97 8 2 FM US FMC Continued...
Page 104: ...Universal IV Installation and Operating Instructions 98 8 2 FM US FMC Continued...
Page 105: ...Control Drawings 99 8 2 FM US FMC Continued...
Page 106: ...Universal IV Installation and Operating Instructions 100 8 2 FM US FMC Continued...
Page 107: ...Control Drawings 101 8 2 FM US FMC Continued...
Page 108: ...Universal IV Installation and Operating Instructions 102 8 2 FM US FMC Continued...