39
8.6
Parameter series 2, action settings
Parameter Description
Settings
2.1
Duration monitoring
NES
1 to 240 seconds
120 sec.
2.2
Impulse function
(parameter 0.1 =
Automatic opening
.1) Inactive during opening
X
.2) Stop during opening
2.3
Automatic close time in
normal operation.
0 = Automatic close deactivated
X
1 to 240 seconds
2.4
Photocell function
when counting down
automatic close time in
normal operation.
.0) Time is started again if the photocell is broken.
X
.1) Once the photocell has been broken for longer than
1.5 seconds, the door will close again after 3 seconds
irrespective of the remaining time.
2.5
Number of re-openings
during automatic close,
and activation of safety
edge
0 to 10
The total will be indefinite if this parameter is set to 0.
0
2.6
Programmable input
.1) Fire alarm test function
X
.2) Switch operating buttons on/off
.3) Works as “mute” function
.4) Input for key switch to bring door back to
intermediate position if this has overrun after power
failure (only possible for DES).
Please note!! Visually check the position of the door to
see if any end positions have been passed.
.5) Software-based override slack cable/pass door
contact (if the door has overrun into the emergency end
switches, the override will remain active as long as the
door remains in the emergency end position).
.6) Switch operating buttons lid on/off.
(External controls remain active).
2.7
Pre-warning close in
normal operation
0 to 60 seconds.
0 sec.
2.8
Pre-warning close in
case of fire, smoke,
battery/power failure
0 to 60 seconds.
0 sec.
2.9
Deactivate photocell
function for particular
range if photocell is
placed in the threshold.
(Only for DES)
.0) Switch off
X
.1) Switch on (place the door in the top position, go to
parameter 2.9 and allow the door to move completely to
the bottom 2x); controller will now remember the