36
8.4
Parameter series 0, basic settings
Parameter Description
Settings
0.0
Exit menu
Exit the menu by pressing “stop/ok”
0.1
Operation mode
.1) “Hold to run” open & close
X
.2) Automatic open, “hold to run” close
.3) Automatic open & close
“hold to run” close not possible with external controls
.4) Automatic open & close
“hold to run” close possible with external controls
.5) Automatic open & close
“hold to run” close with lid and external controls not possible
if the safety edge and/or photocell is/are activated (only
possible using push button on circuit board)
0.2
Safety edge
.1) Automatically detect safety edge
X
.2) Opto sensors
.3) 1.2kΩ DW/air pressure
.4) 8.2kΩ electric safety edge
.5) No safety edge (“hold to run” close)
0.3
Safety edge function
during normal
operation.
(parameter 0.1 = 3 or
4)
.1) Stop and open the door for 2 seconds again after safety
edge activation
X
.2) Stop if safety edge is activated and only continue if the
close button is pressed again.
0.5
Safety edge function
during fire alarm.
(only if par. 0.4=2)
.1) Photocell off - Safety edge off.
X
.2) Photocell off - Safety edge active (Door opens briefly).
Stop if safety edge is activated and continue closing after the
configured time (parameter 0.6).
.3) Photocell off - Safety edge active (Door opens briefly).
Open completely if mains power is present. If mains power is
not present, stop and then close again after the
configured time (parameter 0.6).
.4) Photocell active - Safety edge off.
Stop if Photocell is activated and continue closing after the
configured time (parameter 0.6).
.5) Photocell active - Crush protection off
Open completely if mains power is present.
If mains power is not present, stop and then close again after
the configured time (parameter 0.6).
.6) Photocell active - Safety edge active (Door opens briefly).
Stop if photocell and/or safety edge is activated and continue
closing after the configured time (parameter 0.6).