53
11.1.2
Maintenance instructions
The instructions below must be followed when performing maintenance::
1
Visual inspection controller: Make sure that the controller has no damage or
shortcomings.
2
Make sure that the mains power cable is not damaged. If this is damaged, replace it
with an original cable from the manufacturer.
3
Visual inspection drive unit: Make sure that the drive unit has no damage or
shortcomings.
4
Visual inspection peripherals: Make sure that the peripherals have no damage or
shortcomings.
5
Functional inspection controller: make sure that the door opens, closes and stops
when the appropriate buttons are operated.
6
Functional inspection drive unit: Check if the drive unit runs in the correct direction
when the relevant button is operated, and make sure it does not make any strange
noises.
7
Functional inspection Safety components: Operate the installed safety components
(photocell, light curtain, safety edge protection, etc.) while the door is moving. The
door must stop and go back when this is done.
8
Functioning Fire alarm with mains power: Use the FirePro controller and fire alarm
system to simulate a fire alarm with an open door while there is mains power; the
door must close.
9
Functioning Fire alarm without mains power: Remove mains power, simulate a fire
alarm with open door; the door must close.
10
Replace batteries: Replace the batteries after the year stipulated in the user manual.
11.1.3
Cleaning the device
WARNING
Never use compressed air, scouring sponges, abrasive cleaning products or aggressive liquids like
benzene or acetone to clean the device.
WARNING
Do not use a high-pressure spray jet to clean the device or the area around the device.