24
Table 7 Terminal numbering
Terminal
number
Description
Connect
X1
Mains power
L1, L2, L3, N
X2
Ground
PE
X3
Brake
+ = 4
- = 5
X4
Brake interruption
1 = Com
2 = Nc
X5
Voltage to power supply
L1 = 230 Vac
N = neutral
X6
2 potential-free programmable contacts
Output 1 (par. 5.1) = Terminal 1+2+3
Output 2 (par. 5.2) = Terminal 4+5+6
1 + 4 = Com
2 + 5 = Nc
3 + 6 = No
X7
24 Vdc input for power supply
1 = 24 Vdc
2 = GND
X8
Status battery charger
X9
Connection P-CAP
1 = + 24 Vdc
2 = GND
3 = Light / Siren
X10
Programmable input (potential-free NO contact)
1 = Com
2 = No
X11
Photocell
1 = + 24 Vdc
2 = GND
3 = Com
4 = No
X12
Pass door / slack cable /cable breakage
(resistor or NC contact)
1 = Com 12 Vdc
2 = NC (5k)
X13
Safety edge
1 = + 12 Vdc (Max. 50 Ma)
2 = Resistor (1K2 / 8K2)
3 = Opto
4 = GND
X14
Transmitter LIGI 07 OSE light curtain
1 = + 24 Vdc (Brown)
2 = GND (Blue)
3 = Alignment input (Black)
4 = Synchronization (White)
X15
Receiver LIGI 07 OSE light curtain
1 = + 24 Vdc (Brown)
2 = GND (Blue)
3 = OSE output (Black)
4 = Synchronization (White)
X16
External controls
1 = Common
2 = Stop
3 = Open
4 = Close
5 = Mute
X17
Inputs
1-2 = Sensor (SBS)
3-4 = Escape button
5 = + smoke detectors (4K7)
6 = - smoke detectors (4K7)
7 = 24 Vdc
8 = GND
X18
Fire alarm input 2
1-2 = Fire alarm (8K2)
3-4 = Reset fire alarm
5 = 24 Vdc
6 = GND
X19
Safety brake / Safety features
1 = Com
2 = NC
X20
Drive unit
X21
Control panel lid
X22
RJ 45 connector
X23
DES / NES