41
Parameter Description
Settings
3.9
function of safety edge
and/or photocell after
reaching the maximum
number of attempts
configured in parameter
3.5.
(par. 3.5 > 0)
.1) Continue to close without safety edge.
X
.2) Open again for 2 seconds and then stop
(only possible if mains power is present).
.3) Only stop.
8.8
Parameter series 4, warning settings
Parameter Description
Settings
4.1
Choice door movement in
case of alarm/emergency.
NES:
extra end switch (S6)
and continue closing after
time configured in 4.2
(not possible if par. 3.1 is
set to 2).
DES: intermediate position
par. 4.9.
.1) Door fully closed immediately.
X
.2) Interim stop for extra end switch.
4.2
Waiting time for interim
stop.
(Par. 4.1 = 2).
1 to 240 seconds.
1 sec.
4.3
Choice door movement in
case of fire alarm.
NES: partial opening extra
end switch S6.
(Par. 3.2
≠ 2)
DES: configure
intermediate position in
parameter 4.9.
(Options 2 and 3 can only
be selected if Par. 4.9 is
configured)
.1) Fully close in case of fire alarm 1 and/or 2.
X
.2) Half open in case of fire alarm 1 and fully closed in
case of fire alarm 2.
.3) Half open in case of fire alarm 2 and fully closed in
case of fire alarm 1.
4.4
Choice door movement if
mains power lost
(Par. 4.3 = 2 or 3)
.1 NES) Remains at current position if door is not open
at end position. Close to intermediate position if open
at end position.
X
.2 NES) Closes fully if it is below the position
configured on S6.
.1 DES) Door remains stationary if it is below the
position configured on 1.7.
X
.2 DES) Door closes fully if it is below the