19. Add GND connection information (for SX6730)
Before connecting this device to the power line, the protective earth terminal screws of
this device must be connected to the protective earth in the building installation.
(GND Connection Information):
The building installation shall provide a means for a connection to protective earth;
and the equipment shall be permanently connected to that by a service person.
A SERVICE PERSON shall check whether or not the socket - outlet from which the
equipment is to be powered provides a connection to the building protective earth. If
not, the SERVICE PERSON shall arrange for the installation of a PROTECTIVE
EARTHING CONDUCTOR from the separate protective earthing terminal to the pro-
tective earth wire in the building. The equipment shall be installed in area where equi-
potential bonding exists ((such as a telecommunication centre or a dedicated computer
room).
20. Installation codes
This device must be installed according to the latest version of the country national
electrical codes. For North America, equipment must be installed in accordance to the
applicable requirements in the US National Electrical Code and the Canadian Electri-
cal Code.
21. Interconnection Of Units
Cables for connecting to the unit RS232 and Ethernet Interfaces must be UL
certified type DP-1 or DP-2. (Note- when residing in non LPS circuit)
22. Overcurrent Protection
A readily accessible Listed branch circuit overcurrent protective device rated
20 A must be incorporated in the building wiring.
23. Do Not Use the Switch as a Shelf or Work Space
Caution: Slide/rail mounted equipment is not to be used as a shelf or a work space. The
rails are not intended for sliding the unit away from the rack. It is for permanent instal-
lation at final resting place only, not used for service and maintenance
Summary of Contents for SX6710
Page 1: ...Mellanox SX67X0 1U Switch Systems Hardware User Manual Rev 1 4 www mellanox com...
Page 19: ...Mellanox Technologies 13 Figure 10 BBU Insertion Left and Extraction Right...
Page 68: ...Mellanox Technologies 62 2 3 4 5 6 7 8...
Page 69: ...Mellanox Technologies 63 9 10 11 12 13 14 15...
Page 70: ...Mellanox Technologies 64 16 17 18 19 20 21 WEEE...
Page 72: ...Mellanox Technologies 66 3 4 5 6 7 8 9 45 C 113 F 8 3 PSU...
Page 73: ...Mellanox Technologies 67 10 11 InfiniBand 12 13 14 15 16 InfiniBand...
Page 76: ...Mellanox Technologies 70 27 China CCC Warning Statement...
Page 91: ...Mellanox Technologies 85 7 8 9 10 11 InfiniBand InfiniBand 12 13...