Installation
Mellanox Technologies
8
For Safety Warnings in Turkish see Section E.12, “Montaj Güvenlik Uyar
2.2
Air Flow
Mellanox systems are offered with two air flow patterns:
• Power (rear) side inlet to connector side outlet - marked with blue power supplies/fans-
FRUs’ handles, as shown in Figure 5.
• Connector (front) side inlet to power side outlet - marked with red power supplies/fans
FRUs’ handles, as shown in figure Figure 6.
All servers and systems in the same rack should be planned with the same airflow
direction.
All FRU components need to have the same air flow direction. A mismatch in the air
flow will affect the heat dissipation.
Table 6 provides an air flow color legend and respective OPN designations.
Table 6 - Air Flow Color Legend
Direction
OPN
Designation
Description
R
Connector side inlet to power side outlet.
Red latches are placed on the power inlet
side.
F
Power side inlet to connector side outlet.
Blue latches are placed on the power inlet
side.
Summary of Contents for SX6710
Page 1: ...Mellanox SX67X0 1U Switch Systems Hardware User Manual Rev 1 4 www mellanox com...
Page 19: ...Mellanox Technologies 13 Figure 10 BBU Insertion Left and Extraction Right...
Page 68: ...Mellanox Technologies 62 2 3 4 5 6 7 8...
Page 69: ...Mellanox Technologies 63 9 10 11 12 13 14 15...
Page 70: ...Mellanox Technologies 64 16 17 18 19 20 21 WEEE...
Page 72: ...Mellanox Technologies 66 3 4 5 6 7 8 9 45 C 113 F 8 3 PSU...
Page 73: ...Mellanox Technologies 67 10 11 InfiniBand 12 13 14 15 16 InfiniBand...
Page 76: ...Mellanox Technologies 70 27 China CCC Warning Statement...
Page 91: ...Mellanox Technologies 85 7 8 9 10 11 InfiniBand InfiniBand 12 13...