SG32-UG-EN-V01 Dec 2016
47
1
MTDR100 Specification
Operation
Jog-Dial
Modes
Single-Phase
Low Voltage Prelocation
TDR / Pulse Echo
High Voltage Prelocation
Arc Reflection Multi-shot, Differential Arc
Reflection (DART), Impulse Current (ICE)
ICE Loop On Loop OFF
Ranges
Pulse Echo
Transient Analysis
10 ranges:
Auto, 100m to 55km / 328ft to 34miles
100m to 200km / 328ft to 137miles
Pulse Width
50ns, 100ns, 200ns, 500ns, 1
μ
s, 2
μ
s, 5
μ
s, 10
μ
s
Pulse Amplitude
25V into 50 Ohms
Sampling Rate
100 MHz
Resolution (VP=55%)
0.82m / 2.7ft
Timebase accuracy
200 ppm
Output impedance
50 Ohms
Gain
Variable over 60dB in 5dB steps
Display
Colour, full XGA 1024 x 768: 26.5mm (10.4")
Storage
On-board and USB
Ports:
1 x USB
Software:
CAS-1 (Cable analysis software)
Mains Supply
100 to 240VAC, 45 to 65Hz