6. Connect the crocodile clip or test probe to any
exposed metal.
7. Press and hold the TEST button to start the test.
8. When the test is complete the instrument will display the
results in ohms and indicate a PASS or FAIL.
9. Move to the next piece of exposed metal on the charger and
repeat the test.
10. Repeat until all exposed metal on the charger has been tested.
5.3.3 Interpreting test results
1. The PASS / FAIL limit on the EVCC300 has been set to 0.5 ohms
2. A green tick will indicate a PASS and the resistance will be displayed as shown
18
Tests
www.calcert.com
1.800.544.2843
0
5
10
15
20
25
30