d.
The criteria for the result indication is as follows:
230 V Ph to N (UK / Europe tests)
30 mA AC, 0° and 180°
PASS / FAIL criteria:
PASS:
(
)
RCD trips within 300 ms
FAIL:
(
X
)
No RCD trip in 300 ms
6 mA DC, 0° and 180°
PASS / FAIL criteria:
PASS:
(
)
RCD trips between 3 mA and 6 mA and
within 12.5 seconds
FAIL:
(
X
)
No RCD trip in 12.5 seconds
FAIL:
(
X
)
RCD trips below 3 mA (nuisance trip level)
120 V (USA tests)
6 mA AC, 0° and 180°
PASS / FAIL criteria:
PASS:
(
)
RCD trips within 90 ms
QUESTIONABLE:
(
)
RCD trips between 90 ms to 5.59 seconds
FAIL:
(
X
)
No RCD trip in 5.59 seconds
20 mA AC, 0° and 180°
PASS / FAIL criteria:
PASS:
(
)
RCD trips within 40 ms
QUESTIONABLE:
(
)
RCD trips between 40 ms to 5.59 seconds
FAIL:
(
X
)
No RCD trip in 5.59 seconds