120 V Ph to N (USA tests)
6 mA AC current ramp test
PASS / FAIL criteria:
FAIL:
(
X
)
RCD trips between 0.5 mA to 3.5 mA
QUESTIONABLE:
(
)
RCD trips between 4 mA to 4.5 mA
PASS:
(
)
RCD trips between 5 mA to 6 mA
FAIL:
(
X
)
No RCD trip in 1.2 seconds
20 mA AC current ramp test
PASS / FAIL criteria:
FAIL:
(
X
)
RCD trips between 1 mA to 9 mA
QUESTIONABLE:
(
)
RCD trips between 10 mA to 18 mA
PASS:
(
)
RCD trips between 19 mA and 20 mA
FAIL:
(
X
)
No RCD trip in 2 seconds