5.4.2 How to perform the test
1. Switch the instrument ON.
2. Ensure the mains supply to charger is powered up and on.
3. Plug the EVCC300 into the charger outlet, either directly into
a type 2 connector or using the adaptor provided into a type
1 connector.
Ensure the connection method indicated in the top left corner of
the MENU screen is correct.
As a reminder the menu screen connection indicator looks like
this.
In this screen the EVCC300 is set to direct connection. If the red
cross is not present the instrument is set for connection to the
charger via a tethered cable or plug in charging cable.
4. Use the softkeys 1 and 3 to select the “RCD / GFCI” test
indicated in green.
5. Press softkey 2 to select TEST.
6. On the RCD test screen the left and right softkeys allow the user to highlight either the RCD Type (test type)
or Angle. Press the centre select button to select which you wish to change.
7. Highlight the RCD type and then select the
appropriate current under the personal
protection heading “Pers. prot.:”
21
Tests
www.calcert.com
1.800.544.2843