11-FAULTS/CAUSES/SOLUTIONS
Technical Dept. - All rights reserved - Reproduction is prohibited
ANOMALIES RELATED TO THE HYDRAULIC CIRCUIT
ANOMALY
POSSIBLE CAUSES
SOLUTIONS
No increase in temperature with
stove in operation.
Incorrect combustion adjustment.
Check recipe.
Dirty boiler/system.
Check and clean the boiler.
Low product power.
Check that the product is properly sized for
the requirements of the system.
Poor pellet quality.
Use MCZ pellets.
Condensation in boiler.
Incorrect temperature setting.
Set the product at a higher temperature.
Insufficient fuel consumption.
Check recipe.
Radiators cold in winter.
Room thermostat (local or remote) set
too low. If remote thermostat, check if it
is defective.
Adjust the room thermostat to a higher
temperature, replace it if necessary (if
remote).
Circulator not running because blocked.
Free up the circulator by removing the plug
and turning the shaft with a screwdriver.
Circulator does not run.
Check the electrical connections of the
circulator; replace it if necessary.
There is air in the radiators.
Vent the radiators.
No hot water delivery.
Blocked circulator (pump).
Re-enable the circulator (pump)