11-FAULTS/CAUSES/SOLUTIONS
Technical Dept. - All rights reserved - Reproduction is prohibited
ANOMALY
POSSIBLE CAUSES
SOLUTIONS
The product works for a few minutes
and then switches off.
Start-up phase is not completed.
Repeat start-up.
Temporary power cut.
Wait for the automatic restart.
Clogged smoke duct.
Clean the smoke duct.
Faulty or malfunctioning temperature
probes.
Check and replace the probes.
Faulty ignition plug.
Check the spark plug and replace it, if
necessary.
Pellets accumulate in the brazier, the
glass of the door gets dirty and the
flame is weak.
Insufficient combustion air.
Make sure that the air inlet in the room is
fitted and clear. Check that the combustion
air filter on the Ø 5 cm air inlet pipe is not
clogged. Clean the brazier and check that
all the holes are clear. Perform a general
cleaning of the combustion chamber and
the smoke duct. Check the condition of the
door gaskets.
Damp or unsuitable pellets.
Change the type of pellets.
Faulty smoke evacuation motor.
Check the motor and replace it, if
necessary.
The smoke evacuation motor does
not work.
The product is not electrically powered.
Check the mains current and the protection
fuse.
The motor is faulty.
Check the motor and capacitor and replace
them, if necessary.
Faulty electronic board.
Replace the electronic board.
Faulty control panel.
Replace the control panel.