COMMISSIONING OF D-MAX
2 - 3
SE-46C
Commissioning of the web guide controllers
www.maxcess.eu
MI 1071 1 A
D-MAX OI-N operator interface:
∙
Select menu 1y.5.1.1.1 for S 01 or 1y.5.1.3.1 for S 03
(Hardware IOs
Sensor Setup
S 01 (X5/1) or S 03 (X9/1)
Calibration
1. Reference Value (Lower Limit))
∙
Press the ENTER key
OI-TS operator interface:
∙
Select signal assignment 10mA
D-MAX OI-N operator interface:
∙
2. Reference Value (Upper Limit))
∙
Press the ENTER key
∙
Press the ENTER key to save the calibration
1.4. Calibrating the position
signal on the D-MAX
controller
Depending on how the sensor is connected to the D-MAX
Controller, perform the calibration for:
– S 02 - Position signal (menu 1y.5.1.2) if the SE-46 sensor is
connected to input X5
or for
– S 04 - Position signal (menu 1y.5.1.4) if the SE-46 sensor is
connected to input X9
OI-TS operator interface:
∙
Select signal assignment 0mA