COMMISSIONING OF DP-20/DP-30
3 - 2
SE-46C
Commissioning of the web guide controllers
www.maxcess.eu
MI 1071 1 A
Inbetriebnahme
DP-2
030.fm
∙
Continue pressing the Sensor key until sensor line centre -
ý
is selected (menu 3D)
1.2. Call menu 1K.8.3
Simulate Analog Signals
on
the SE-46C
The analog signals required for the calibration are simulated by
sensor SE-46C.
OI-TS operator interface:
∙
Select menu 1K.8.3
Simulate Analog Signals
(Press the 6 button and hold it for 2sec.
Press the 8 button
Startup
Press the 3 button Simulate Analog Signals)
∙
Press the Return button to confirm the information in the
display
1.3. Calibrating the locking
signal on the DP-20/DP-30
web guide controller
DP-20/DP-30 web guide controller:
∙
Select menu 3D.1.4.1
Select Sensor
(Manual
Basic
Calibration
Select Sensor)
∙
DP-20 controller:
select
(X4)
DP-30 controller:
select
(X5)
(line sensor - line centre
ý
)
∙
Press the ENTER key
OI-TS operator interface:
∙
Select signal assignment 0mA
DP-20/DP-30 web guide controller:
∙
Determine the first reference value
∙
Press the ENTER key
G
G