COMMISSIONING OF DP-20/DP-30
3 - 5
SE-46C
Commissioning of the web guide controllers
www.maxcess.eu
MI 1071 1 A
2.3. Switching on ASC
locking
DP-20/DP-30 web guide controller:
∙
DP-20 controller: select menu 3D.5.1
DP-30 controller: select menu 3D.5.2
(Manual
Custom
ASC Control)
∙
Set the status of
ASC locking
to
ON
3. Setting the polarity and
gain
Note:
Settings must be made for sensor mode D - Line centre
ý
.
3.1. Setting polarity
The guiding direction (polarity) must be checked depending on
the mechanical installation direction of the system and adjusted
if necessary.
DP-20/DP-30 web guide controller:
∙
Select men
u
3D.1.3
(Manual
Basic
Polarity)
∙
Set the
polarity
3.2. Setting gain
Gain must be set optimally.
DP-20/DP-30 web guide controller:
∙
Select men
u
3D.1.1
(Manual
Basic
Gain)
∙
Set the
gain
Operation
Note:
The DP-20/DP-30 web guide controller must be operated in
„Automatic“ mode with sensor mode D - Line centre
ý
.