COMMISSIONING OF FIFE-500
4 - 1
SE-46C
Commissioning of the web guide controllers
www.maxcess.eu
MI 1071 1 A
Inbetr
iebna
hme Fife-500.fm
4 COMMISSIONING OF FIFE-500
FIFE-500 Web Guide
Controller
Note:
Detailed information about sensor calibration is available in the
„FIFE-500 Operating Instructions“.
Precondition:
The SE-46C sensor must be connected to the FIFE-500 web
guide controller according to the system diagram in the system
documentation.
The SE-46C is operated from the OI-TS operator interface.
1. Calibrating the analog
signal inputs of the FIFE-500
controller
1.1. Preparing the FIFE-500
controller for the calibration
FIFE-500 operator interface:
∙
Press the Manual button to set „Manual“ operating mode
∙
Select menu 1x.2.2
Control Options
(Press Setup button
Press Right Arrow button
Press
Control Options
button)
∙
Set the
sensor type
to Line
∙
Press the
ENTER button
∙
Press the RETURN button to return to the operator level
Figure 4.1: OI-TS Operating
Interface