COMMISSIONING OF D-MAX
2 - 2
SE-46C
Commissioning of the web guide controllers
www.maxcess.eu
MI 1071 1 A
Inbetr
iebna
hme D-M
AX.fm
The entry changes in the second place of the menu
identification depending on the job selected.
Note:
If the job cannot be selected with y = 'J' or y = 'K' , the
software of the D-MAX controller has not been prepared
for analog sensor signals. Please check the system documentation!
The calibration process cannot be continued.
1.2. Call menu 1K.8.3
Simulate Analog Signals
on
the SE-46C
The analog signals required for the calibration are simulated by
sensor SE-46C.
OI-TS operator interface:
∙
Select menu 1K.8.3
Simulate Analog Signals
(Press the 6 button and hold it for 2sec.
Press the 8 button
Startup
Press the 3 button Simulate Analog Signals)
∙
Press the RETURN button to confirm the information in the
display
1.3. Calibrating the locking
signal on the D-MAX
controller
Depending on how the sensor is connected to the D-MAX
controller, perform the calibration for:
– S 01 - Locking signal (menu 1y.5.1.1) if the SE-46C sensor is
connected to input X5
or for
– S 03 - Locking signal (menu 1y.5.1.3) if the SE-46C sensor is
connected to input X9.
OI-TS operator interface:
∙
Select signal assignment 0mA