COMMISSIONING OF FIFE-500
4 - 2
SE-46C
Commissioning of the web guide controllers
www.maxcess.eu
MI 1071 1 A
∙
Press the SENSOR button until sensor line centre -
ý
is
selected (menu 1E)
1.2. Call menu 1K.8.3
Simulate Analog Signals
on
the SE-46C
The analog signals required for the calibration are simulated by
sensor SE-46C.
OI-TS operator interface:
∙
Select menu 1K.8.3
Simulate Analog Signals
(Press the 6 button and hold it for 2sec.
Press the 8 button
Startup
Press the 3 button Simulate Analog Signals)
∙
Press the RETURN button to confirm the information in the
display
1.3. Calibrating the locking
signal on the FIFE-500 web
guide controller
FIFE-500 operator interface:
∙
Select menu 1E.1.7
Sensor Setup
(Press Setup button
Press Sensor Setup button)
∙
Press the START CALIBRATION button
OI-TS operator interface:
∙
Select signal assignment 0mA
FIFE-500 operator interface:
∙
Press the button to determine the first reference value