10.0
TROUBLESHOOTING
www.maxcessintl.com
MAGPOWR Spyder-Plus
MI 850A320 1 M
Page 38 of 60
10.2
Tuning Problems (Load Cell Control)
Problem
Possible Cause
Solution or Diagnostic
Tension unstable
Control not optimally
tuned.
Use Quick Stabilize.
Navigate to the
QuickStab
menu. Press the
key and then press
If Unstable
to immediately try to stabilize.
Review “
Tuning
” once stability is obtained.
See Section 6.4.
“Cannot be stabilized.”
Appears while using quick
stabilize.
To diagnose:
1) Go to the
Output Level
screen to read the
average output while running in AUTO mode.
2) Set the
Manual Level
to the average value.
3) Go to the
Tension
screen.
4) Toggle between AUTO and MANUAL
modes.
If the tension in MANUAL mode is
NOT
more
stable than the tension in AUTO mode, the
tension variations being observed are not
caused by dynamic instability. They are
disturbances generated by your process.
The message “Re-Tune P at
core” repeatedly appears
The system is less stable
at some intermediate roll
diameter than it is at core.
When the message appears retune P at the
present diameter rather than at core.