![Max Phantom 2000 Installation And Owner'S Manual Download Page 38](http://html1.mh-extra.com/html/max/phantom-2000/phantom-2000_installation-and-owners-manual_1742742038.webp)
36
Power
INPUTS
MC-100
JOG
RIGHT
JOG
LEFT
UL
Entrap
Matrix
On Line
ERD
Sensitivity
Photo
Cell
Limit SW
On Line
Edge 2
Edge 1
Edge 1
Edge 2
Photo Cell
GND
Jog R
T
Jog L
T
MOTOR OVERLOAD
Motor Controller
ERD
Min
Max
Sensitivity
1
1
5
V
AC
ON
POWER
OF
F
MA
X P
S-2
4
PO
WE
R SUPP
LY
FU
SE
7 A
MP
IN
Ma
de
in
USA
POW
ER
IN
PO
WER
/SO
LAR
IN
BAT
TERY
IN
ww
w.
max.
us.co
m
Mad
e in
US
A
BA
TTE
RY
PAC
K
TO M
OTO
R
CO
NTR
OLL
ER
E
1/2
Ba
ttery
Vo
ltag
e
Rep
lace
Ba
ttery
TEST
Ba
ttery
ON/O
FF
Ba
ttery
Ba
ttery
IN
Erro
r
F
MAX BC
-7
Ba
ttery
Mod
ule
Po
we
r
IN
PU
TS
MC
-10
0
JOG
RI
GHT
JO
G
LEF
T
UL
En
trap
Mat
rix
On
Lin
e
ER
D
Se
ns
itivity
Ph
oto
Cel
l
Lim
it SW
On
Li
ne
Ed
ge
2
Ed
ge
1
Ed
ge
1
Ed
ge
2
Ph
oto
Ce
ll
GN
D
Jo
g RT
Jo
g L
T
M
OTO
R
OVER
LO
AD
M
ot
or
C
ont
rol
ler
ER
D
Mi
n
Ma
x
Turn knob clockwise until
green LED lights up
(Max sensitivity reached) . . .
Position gate half-way open and
STOP
gate.
This gate position will put the most amount of
resistance on the ERD sensor when gate cycles.
Turn knob counter-clockwise
to reduce sensitivity as
needed (LED will turn OFF).
Allow the gate to strike an immobile object while
OPENING
and
CLOSING
. The gate
MUST
reverse direction
after striking the object. If it does not, increase the
ERD Sensitivity
. Repeat this process until the correct
sensitivity is set. If alarm sounds while preforming this procedure, press alarm reset button on control box.
NOTE:
When solid gates are installed in
unusually high wind areas
, ERD sensor can be set to
Min
to keep
the gate cycling normally in such extreme conditions.
CAUTION:
Minimum sensitivity setting results in gate exerting
MAXIMUM force
before reversing direction.
Adjust ERD Sensitivity
Test ERD Sensitivity
The Phantom 2000 is equipped with an
ERD Sensor
-
Electronic Reversing Device
(Type A) that functions as the primary
entrapment protection according to UL 325 standards.
The gate will reverse direction after encountering an obstruction in
either the OPEN or CLOSE gate cycle
.
When the gate encounters an obstruction during the
CLOSE
cycle, it will reverse to the open position and
PAUSE
the gate. An
input command (press remote button or exit loop) is needed
BEFORE
the gate will reset and close again.
When the gate encounters an obstruction during the
OPEN
cycle, it will reverse approximately 6 inches and
PAUSE
the gate. An
input command (press remote button or exit loop) is needed
BEFORE
the gate will reset and open again.
For the
ERD Sensitivity
to function correctly:
•
THE RELEASE HANDLE CLAMP MUST NOT SLIP
when the gate encounters an obstruction.
•
Limit switches must be learned
BEFORE
adjusting the ERD Sensitivity.
Adjustments
reverse sensor (erd)
MC-100 motor controller
ERD
Sensitivity
Min
Max
Sensitivity
ERD
Sensitivity
Min
Max
Sensitivity
x
sitiv
ax
ensitiv
a
Sensiti
a
Sensit
M
Sensi
M
Sens
M
Sen
M
S
Alarm Reset
Button
STOP Gate
STOP Gate
Half-way
Half-way
CLOSE
gate. If ERD sensor triggers, reduce
sensitivity. If sensor does
NOT
trigger,
sensitivity is set correctly.
CLOSE Gate
CLOSE Gate
1
2
Summary of Contents for Phantom 2000
Page 2: ......
Page 14: ...12 MAX Solar Panel Approx 45 solar installation Refer to Solar application guide...
Page 45: ...43...