7 Analog Control
44
R4G/R4GE series
7-3-3
Current Program Setting with External Resistance
The output current can be controlled with an external voltage. (Set SW1-6 to OFF.)
(Input voltage 0 to 10Vdc corresponds to the output current 0 to the rating.)
Check that the current setting mode is set to Remote mode.
(Refer to [7-2 Switching Local/Remote Mode (Voltage/Current Mode Setting].)
7-3-4
Current Program Setting with External Resistance
The output current can be controlled with an external resistance. (Set SW1-5 to ON and SW1-6 to
OFF.)
(Resistance value 0 to 10kΩ corresponds to the output current 0 to the rating.)
Check that the current setting mode is set to Remote mode.
(Refer to [7-2 Switching Local/Remote Mode (Voltage/Current Mode Setting].)
TB1
2
5
Internal circuit
+
0 to 10Vdc
SW1
ON
1
2
3
4
5
6
7
8
+S
(common)
TB1
2
5
Internal circuit
SW1
ON
1
2
3
4
5
6
7
8
0 to approx.
10kΩ
+
1mA
-
+S
(common)