![Masoneilan SVI II ESD Installation And Maintenance Manual Download Page 92](http://html.mh-extra.com/html/masoneilan/svi-ii-esd/svi-ii-esd_installation-and-maintenance-manual_1735323092.webp)
© 2017 Baker Hughes, a GE company, LLC. All rights reserved.
92
|
BHGE
Figure 58 Configuration Pushbutton Guide
ATO
Setup
+
+
+
*
*
*
Air to....Menu
CONFIGuration Menu
ATC
*
PSI
*
*
BAR
KPA
ENGLISH
*
*
FRENCH
+/-
Pressure Units
Menu
Language
Menu
Air to
Menu
CONFIG
CONFIG
Language
Menu
Pressure
Menu
Units
+
Select display language.
Select display
units for pressure.
Select Air To Open (ATO)
or Air To Close (ATC). Must
match the actuator exactly.
Press * to select option.
Press + or - to accept and
proceed to next menu item.
SPANISH
PORTUGUESE
JAPANESE
ITALIAN
GERMAN
*
*
*
*
*
See Figure 62 on
page 107 for full menu
Summary of Contents for SVI II ESD
Page 4: ...This page intentionally left blank ...
Page 10: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 100: ...This page intentionally left blank ...
Page 120: ...This page intentionally left blank ...
Page 126: ...This page intentionally left blank ...
Page 160: ...This page intentionally left blank ...
Page 194: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 204: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 208: ...This page intentionally left blank ...