Single Acting PST Controller
WARNING
Isolate the valve from the process and disconnect air tubing from
the PST controller. Disconnect air fully to avoid injury or process
damage.
The supply and output connections for the SVI II ESD, located on bottom of the pneumatic
block, are 1
⁄
4" NPT threaded. Output is toward the front, supply is toward the back.
Maximum allowable air supply pressure to the SVI II ESD varies according to actuator, valve
size, and valve type. Refer to the serial plate of the valve to know the specified supply
pressure; it must never be less than the maximum spring pr10 psi.
1. Install the tubing to the air supply port (
S
).
2. For a single acting actuator - pipe the outbound air from the output pressure port (
I
)
to
the actuator.
3. Air supply:
Supply pressure for single acting SVI II ESD:
30 -120 psi (2.07 - 8.28 bar) (207- 827.6 kPa)
Minimum tubing diameter 1
⁄
4" (6mmx4mm)
Figure 50 Air Ports on Single Acting PST Controller
Output
Supply
Summary of Contents for SVI II ESD
Page 4: ...This page intentionally left blank ...
Page 10: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 100: ...This page intentionally left blank ...
Page 120: ...This page intentionally left blank ...
Page 126: ...This page intentionally left blank ...
Page 160: ...This page intentionally left blank ...
Page 194: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 204: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 208: ...This page intentionally left blank ...