This page contains parameters related to Measure like Input Type, Input
Range, Scaling and Transfer Function. The Description of the
Parameters appear on this page is given below.
Parameter Name
Description / Options
I/P Type
(Input Type)
Measure Input Type
Available Options:
mA : 0.000 to 24.000 mA DC
mA(24V) : 0.000 to 24.000 mA DC
mV : 0.00 to 250.00 mV DC
V : 0.000 to 30.000 V DC
Input Range
Low (0%)
Low Range for Measure Input.
Range:
Default Input Low to
Input Range High(100%)
This parameter is enabled, if
Main Display
in
MENU
DISPLAY
MEASURE
is set to
Percentage
or
Scaled.
Input Range
High (100%)
High Range for Measure Input.
Range:
Input Range Low(0%)
to Default Input High
This parameter is enabled, if
Main Display
in
MENU
DISPLAY
MEASURE
is set to
Percentage
or
Scaled.
Scaled Input Range
Low(0%)
Scaling Low Range for Measure Input.
Range:
-99999 to
Scaled Input Range High(100%)
Decimal Point for this EditBox can be changeable.
This parameter is enabled, if
Main Display
in
MENU
DISPLAY
MEASURE
is set to
Scaled.
Scaled Input Range
High(100%)
Scaling High Range for Measure Input.
Range:
Scaled Input Range Low(0%)
to 99999
Decimal Point for this EditBox can be changeable.
This parameter is enabled, if
Main Display
in
MENU
DISPLAY
MEASURE
is set to
Scaled.
TF
(Transfer Function)
Transfer Function for Scaling
Available Options:
Linear
x^2 (x
2
)
x^(1/2) (
√x)
This parameter is enabled, if
Main Display
in
MENU
DISPLAY
MEASURE
is set to
Scaled.