P a g e
|
31
of
52 User Manual
TF
(Transfer Function)
Transfer Function for Scaling
Available Options:
Linear
x^2 (x
2
)
x^(1/2) (
√x)
This parameter is enabled, if
Main Display
in
MENU
DISPLAY
SOURCE
is set to
Scaled.
Source Type
Source Output Format
Available Options:
STEP
RAMP
At a time one can be selectable.
Press F1 key on the one of the option for more settings.
4.2.1 STEP Page
Parameter Name
Description / Options
Manual
(Output Type)
Step Manual Mode Selection CheckBox.
Ticking this checkbox will enable Step Manual Mode. And Un-ticking will enable Auto
Step Mode.
Step Time (s)
Enter the time for a single step in seconds,
Range:
1 to 9999
This parameter is enabled only for Auto Step Mode (Manual CheckBox is
Un-Checked)
Step(unit)
Step Size in unit
Step Size in unit, where unit is changed according to current Output Type and Source
Display Mode.
Only Specify one Step(unit) or Step(%), the other will automatically changed
according to the changed parameter.
Range:
In accordance with Output Range & Source Display Mode.
This parameter is disabled, if
Main Display
in
MENU
DISPLAY
SOURCE
is set
to
Percentage.
Step(%)
Step Size in Percentage.