© Welbilt, Inc.
Harvest – Condensing Unit
88
Indigo NXT QuietQube/CVD: Sequence of Operation
Suction Pressure remains higher than the low
pressure control cut-out (12 psig) and the
compressor continues to run.
Discharge pressure remains below the fan cycle
control cut-out setting and the condenser fan
motor remains off.
Discharge
Gas
Discharge
Gas to
Receiver
6
Harvest
Bin Switch
5
Purge
45 Sec
Harvest
4
Freeze
Ice Thickness
Probe
3
Pre-Chill
120 Sec.
(first cycle)
30 Sec.
(thereafter)
1
Purge
45 Sec
Equalize
5 Sec
Start
5 Sec
2
7 Minute Max
Summary of Contents for Welbilt Indigo NXT QuietQube
Page 3: ... Welbilt Inc Welbilt Inc Engineered For Ease Overview INDIGO NXT 3 ...
Page 17: ... Welbilt Inc Welbilt Inc Engineered For Ease QuietQube CVD Installation INDIGO NXT 17 ...
Page 50: ... Welbilt Inc Engineered For Ease Menu Navigation Indigo NXT Ice Machines ...
Page 54: ... Welbilt Inc Indigo NXT Menu Navigation Alert 54 Touch Screen Interface Main Menu ...
Page 55: ... Welbilt Inc Indigo NXT Menu Navigation Alert 55 Touch Screen Interface Main Menu ...
Page 114: ... Welbilt Inc Welbilt Inc Engineered For Ease Troubleshooting INDIGO NXT Ice Machine 114 ...
Page 126: ... Welbilt Inc Welbilt Inc Engineered For Ease Troubleshooting Tips INDIGO NXT Ice Machine 126 ...
Page 153: ... Welbilt Inc Water Level Probe Diagnostics 153 Indigo NXT Ice Machine Troubleshooting Tips ...