Ice Thickness Probe Operation (ITP)
84
Indigo NXT QuietQube/CVD: Sequence of Operation
• The Ice Thickness Probe (ITP)
senses ice on the evaporator
and signals the control board
to start a harvest cycle.
• At the start of every freeze
cycle the Ice Machine is
locked into a 6 Minute Freeze
cycle
• The 6 Minute Lock in can be
overridden only by the
manual harvest through the
interface display.
• When the ITP comes in
contact with the ice and after
the 6 minute Lock in, the ice
machine will go into harvest.
1/8” Bridge
thickness of ice