© Welbilt, Inc.
Freeze – Condensing Unit
82
Indigo NXT QuietQube/CVD: Sequence of Operation
Suction Pressure remains higher than the
low pressure control cut-out (12 psig) and
the compressor continues to run.
Discharge pressure remains higher than
the fan cycle control cut-out setting and
the condenser fan motor continues to
run.
4
Freeze
Ice Thickness
Probe
3
Pre-Chill
120 Sec.
(first cycle)
30 Sec.
(thereafter)
1
Purge
45 Sec
Equalize
5 Sec
Start
5 Sec
2
35 Minute Max