Ice Thickness Probe Diagnostics
140
Indigo NXT Ice Machine Troubleshooting Tips
Should be adjusted to maintain 1/8” ice bridge
thickness
In order to achieve proper bridge thickness the
gap
between the flat part of the ITP and the
grid should be set to
9/32” (7mm) with no
ice on it as shown
.
Adjustment
Screw
Cube Cells
Probe Gap
9/32”
1/8” Bridge”
Microphone
Function:
The ice thickness probe sense ice on the
evaporator and signals the control board to start a
harvest cycle.
NOTE: The Ice Machine incorporates a 6 minute freeze
lock-in feature to prevent the ice machine from short
cycling in and out of harvest.