Refrigerant Recovery/Evacuation
NORMAL SELF-CONTAINED PROCEDURES
Do not purge refrigerant to the atmosphere. Capture
refrigerant using recovery equipment. Follow the
manufacturer’s recommendations.
CONNECTIONS
Manifold gauge sets must utilize low loss fittings to
comply with U.S. Government rules and regulations.
Make these connections:
•
Suction side of the compressor through the suction
service valve.
•
Discharge side of the compressor through the
discharge service valve.
Important
Manitowoc Ice assumes no responsibility for the use
of contaminated refrigerant. Damage resulting from
the use of contaminated refrigerant is the sole
responsibility of the servicing company.
Important
Replace the liquid line drier before evacuating and
recharging. Use only a Manitowoc (OEM) liquid line
filter-drier to prevent voiding the warranty.
Summary of Contents for RNS012
Page 2: ......
Page 8: ......
Page 26: ...18 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 32: ...24 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 48: ...40 Part Number STH044 10 13 9 Lift out ice damper ...
Page 49: ...Part Number STH044 10 13 41 10 Lift out ice strainer ramp ...
Page 50: ...42 Part Number STH044 10 13 11 Turn ice wiper counterclockwise to remove ...
Page 56: ...48 Part Number STH044 10 13 19 Remove ice dispensing wheel by lifting straight out ...
Page 57: ...Part Number STH044 10 13 49 20 Water Reservoir Cover Removal A Push up on cover to snap off ...
Page 62: ...54 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 110: ...102 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 116: ...108 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 122: ...114 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 123: ......