DRAIN CONNECTIONS
Follow these guidelines when installing drain lines to
prevent drain water from flowing back into the ice
machine and storage bin:
•
Drain lines must have a 1.5 in. (3.8 cm) drop per 5
ft. of run (2.5 cm per meter), and must not create
traps.
•
The floor drain must be large enough to
accommodate drainage from all drains.
•
Run separate bin and water-cooled condenser
drain lines. Insulate them to prevent condensation.
•
Vent the bin drain to the atmosphere. Do not vent
the condenser drain on water-cooled models.
•
Drains must have a union or other suitable means
to allow a place of disconnection from the ice
machine when servicing is required.
Summary of Contents for RNS012
Page 2: ......
Page 8: ......
Page 26: ...18 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 32: ...24 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 48: ...40 Part Number STH044 10 13 9 Lift out ice damper ...
Page 49: ...Part Number STH044 10 13 41 10 Lift out ice strainer ramp ...
Page 50: ...42 Part Number STH044 10 13 11 Turn ice wiper counterclockwise to remove ...
Page 56: ...48 Part Number STH044 10 13 19 Remove ice dispensing wheel by lifting straight out ...
Page 57: ...Part Number STH044 10 13 49 20 Water Reservoir Cover Removal A Push up on cover to snap off ...
Page 62: ...54 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 110: ...102 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 116: ...108 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 122: ...114 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 123: ......