90
Part Number STH044 10/13
Relay Operation Check
1. Disconnect wires from relay terminals.
2. Verify the contacts are closed.
Measure the resistance between terminals 1 and
2. No continuity indicates open contacts. Replace
the relay.
3. Check the relay coil.
Measure the resistance between terminals 2 and
5. No resistance indicates an open coil. Replace
the relay.
4. Move toggle switch to the ICE position.
5. The compressor start winding should energize for
less than 1 second. Continued high amperage
draw could indicate:
•
Low incoming power supply.
(Check voltage at compressor start-up when load
is greatest.)
•
Defective relay.
•
Defective capacitor.
•
Defective compressor.
6. Verify voltage and replace all start components.
7. If all of the previous tests are satisfactory and the
compressor will not operate or continue to
operate, replace the compressor.
!
Warning
Disconnect electrical power to the ice machine
before proceeding.
Summary of Contents for RNS012
Page 2: ......
Page 8: ......
Page 26: ...18 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 32: ...24 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 48: ...40 Part Number STH044 10 13 9 Lift out ice damper ...
Page 49: ...Part Number STH044 10 13 41 10 Lift out ice strainer ramp ...
Page 50: ...42 Part Number STH044 10 13 11 Turn ice wiper counterclockwise to remove ...
Page 56: ...48 Part Number STH044 10 13 19 Remove ice dispensing wheel by lifting straight out ...
Page 57: ...Part Number STH044 10 13 49 20 Water Reservoir Cover Removal A Push up on cover to snap off ...
Page 62: ...54 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 110: ...102 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 116: ...108 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 122: ...114 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 123: ......