72
Part Number STH044 10/13
Suction Pressure Low Checklist
Problem
Cause
Improper
installation
Refer to “Installation/Visual Inspection
Checklist.”
Discharge
pressure
Discharge pressure is too low and is
affecting suction pressure. Refer to
“Discharge Pressure Low Checklist.”
Improper
refrigerant
charge
Undercharged
Wrong type of refrigerant
Other
Non-Manitowoc components in system
Restricted/plugged liquid line drier
Restricted/plugged tubing in suction side of
refrigeration system
Expansion valve starving
No water or insufficient pressure
Moisture in refrigeration system
Dirty Evaporator
NOTE: Do not limit your diagnosis to only the items
listed in the checklists
Summary of Contents for RNS012
Page 2: ......
Page 8: ......
Page 26: ...18 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 32: ...24 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 48: ...40 Part Number STH044 10 13 9 Lift out ice damper ...
Page 49: ...Part Number STH044 10 13 41 10 Lift out ice strainer ramp ...
Page 50: ...42 Part Number STH044 10 13 11 Turn ice wiper counterclockwise to remove ...
Page 56: ...48 Part Number STH044 10 13 19 Remove ice dispensing wheel by lifting straight out ...
Page 57: ...Part Number STH044 10 13 49 20 Water Reservoir Cover Removal A Push up on cover to snap off ...
Page 62: ...54 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 110: ...102 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 116: ...108 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 122: ...114 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 123: ......