DIAGNOSING START COMPONENTS
If the compressor attempts to start, or hums and trips
the overload protector, check the start components
before replacing the compressor.
Capacitor
Visual evidence of capacitor failure can include a
bulged terminal end or a ruptured membrane. Do not
assume a capacitor is good if no visual evidence is
present. A good test is to install a known good
substitute capacitor. Use a capacitor tester when
checking a suspect capacitor. Clip the bleed resistor
off the capacitor terminals before testing.
Relay
The relay has a set of contacts that connect and
disconnect the start capacitor from the compressor
start winding. The contacts on the relay are normally
closed (start capacitor in series with the start winding).
The relay senses the voltage generated by the start
winding and opens the contacts as the compressor
motor starts. The contacts remain open until the
compressor is de-energized.
Summary of Contents for RNS012
Page 2: ......
Page 8: ......
Page 26: ...18 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 32: ...24 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 48: ...40 Part Number STH044 10 13 9 Lift out ice damper ...
Page 49: ...Part Number STH044 10 13 41 10 Lift out ice strainer ramp ...
Page 50: ...42 Part Number STH044 10 13 11 Turn ice wiper counterclockwise to remove ...
Page 56: ...48 Part Number STH044 10 13 19 Remove ice dispensing wheel by lifting straight out ...
Page 57: ...Part Number STH044 10 13 49 20 Water Reservoir Cover Removal A Push up on cover to snap off ...
Page 62: ...54 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 110: ...102 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 116: ...108 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 122: ...114 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Page 123: ......