SUCTION TEMPERATURE LOW CHECKLIST
Improper Installation
•
Refer to “Installation/Visual Inspection Checklist”
(page 102)
Discharge Temperature
•
Discharge temperature is too low and is affecting
low side – refer to “Freeze Cycle Discharge
Temperature Low Checklist” (page 108)
Improper Refrigerant Charge
•
Undercharged
•
Wrong type of refrigerant
Other
•
Non-Manitowoc components in system
•
Improper water supply over evaporator – refer to
“Water System Checklist” (page 103)
•
Restricted/plugged liquid line drier
•
Restricted/plugged tubing in suction side of
refrigeration system
•
TXV starving - continue the table