Part N
umber ST
H038 5/12
97
Suction Line Temperature
3 minutes into the freeze
cycle
Normal or High
Normal or High
Low
Normal or High
Freeze Cycle
Suction Temperature
_______ ______ _____
1 minute Middle End
If suction temperature is High or Low refer to freeze cycle high or low suction temperature problem
checklist page 109 to eliminate problems and/or components not listed on this table before proceeding.
Suction temperature is
High
Suction temperature is
Low or Normal
Suction temperature is
High
Suction temperature is
High
Wait 5 minutes into the
freeze cycle.
Compare temperatures of
evaporator inlet
and
evaporator outlet.
Inlet _____________°C
Outlet ___________ °C
Difference________ °C
Inlet and outlet
within 4°C
of each other
Inlet and outlet
not within 4°C
of each other
-and-
Inlet is colder than
outlet
Inlet and outlet
within4°C
of each other
-or-
Inlet and outlet
not within 4°C
of each other
-and-
Inlet is warmer than
outlet
Inlet and outlet
within 4°C
of each other
SINGLE EXPANSION VALVE SELF CONTAINED AIR and WATERCOOLED CONDENSER
Operational Analysis
1
2
3
4
Summary of Contents for I0320A
Page 20: ...18 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Page 26: ...24 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Page 86: ...84 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Page 124: ...122 Is the evaporator dirty Dry evaporator first then check YES NO NO ...
Page 174: ...172 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Page 176: ...174 Part Number STH038 5 12 I0320 Self Contained 1 Ph ...
Page 177: ...Part Number STH038 5 12 175 I0500 Self Contained 1 Ph ...
Page 180: ...178 Part Number STH038 5 12 ...
Page 181: ......