Part Number STH038 5/12
107
FREEZE CYCLE DISCHARGE TEMPERATURE
HIGH CHECKLIST
Improper Installation
•
Refer to “Installation/Visual Inspection Checklist”
(page 102)
Air Condenser
•
Dirty condenser filter
•
Dirty condenser fins
•
High inlet air temperature
•
Condenser discharge air recirculation
•
Defective fan cycling control (page 154)
•
Defective fan motor
Other
•
Overcharged
•
Non-condensable (air) in system
•
Wrong type of refrigerant
•
Non-Manitowoc components in system
•
High side refrigerant lines/component restricted