WATER TROUGH OVERFILLING DURING THE
FREEZE CYCLE
Step 1
Press the power button and turn off the ice
machine.
Step 2
If water continues to flow with the ice machine
off, disconnect power. If water continues to flow verify
water pressure is below 80 psig before replacing the
water inlet valve.
Step 3
Check water level probe mounting and verify
secure wiring connections at the probe and control
board.
Step 4
Scroll to Service/Diagnostics/Inputs and press
down arrow until Wtr Low and Wtr High are displayed.
•
No is displayed - Control board is not receiving a
sensing water signal. Continue with step 5.
•
Yes is displayed - Control board is receiving a
sensing water signal. Clean the water level probe
and test run.
Step 5
Start a new freeze cycle by pressing the
power button.
Step 6
Wait until the pre-chill cycle begins, then
jumper water level probe connection #2 & #3 at the
control board.
A. Water level light energizes and water flow
stops - Repair wire or replace water level
probe.
B. Water level light does not energize and water
continues to flow - Replace control board.
Summary of Contents for I0320A
Page 20: ...18 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Page 26: ...24 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Page 86: ...84 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Page 124: ...122 Is the evaporator dirty Dry evaporator first then check YES NO NO ...
Page 174: ...172 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Page 176: ...174 Part Number STH038 5 12 I0320 Self Contained 1 Ph ...
Page 177: ...Part Number STH038 5 12 175 I0500 Self Contained 1 Ph ...
Page 180: ...178 Part Number STH038 5 12 ...
Page 181: ......