PTCR Operation Check
1. Visually inspect the PTCR. Check for signs of
physical damage.
NOTE:
The PTCR case temperature may reach
100°C while the compressor is running. This is normal.
Do not change a PTCR just because it is hot.
2. Wait at least 10 minutes for the PTCR to cool to
room temperature.
3. Remove the PTCR from the ice machine.
4. Measure the resistance of the PTCR as shown.
The resistance reading must be between 18 and
40 ohms
Measure Resistance At Ends
PTCR