DIAGNOSING START COMPONENTS
If the compressor attempts to start, or hums and trips
the overload protector, check the start components
before replacing the compressor.
Capacitor
Visual evidence of capacitor failure can include a
bulged terminal end or a ruptured membrane. Do not
assume a capacitor is good if no visual evidence is
present. A good test is to install a known good
substitute capacitor. Use a capacitor tester when
checking a suspect capacitor. Clip the bleed resistor
off the capacitor terminals before testing.
•
If the compressor attempts to start, or hums and
trips the overload protector, check the starting
components before replacing the compressor.
•
Visual evidence of capacitor failure can include a
bulged terminal end or a ruptured membrane. Do
not assume a capacitor is good if no visual
evidence is present.
•
A good test is to install a known good substitute
capacitor.
•
Use a capacitor tester when checking a suspect
capacitor. Clip the bleed resistor off the capacitor
terminals before testing.
Summary of Contents for I0320A
Page 20: ...18 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Page 26: ...24 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Page 86: ...84 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Page 124: ...122 Is the evaporator dirty Dry evaporator first then check YES NO NO ...
Page 174: ...172 Part Number STH038 5 12 This Page Intentionally Left Blank ...
Page 176: ...174 Part Number STH038 5 12 I0320 Self Contained 1 Ph ...
Page 177: ...Part Number STH038 5 12 175 I0500 Self Contained 1 Ph ...
Page 180: ...178 Part Number STH038 5 12 ...
Page 181: ......