ICE THICKNESS PROBE (HARVEST INITIATION)
FUNCTION
The ice thickness probe senses ice on the evaporator
and signals the control board to start a harvest cycle.
After ice forms on the evaporator, the ice will contact
the ice thickness probe and a harvest cycle is initiated.
SPECIFICATIONS
Freeze Time Lock-In Feature
The ice machine control system incorporates a freeze
time lock-in feature. This prevents the ice machine
from short cycling in and out of harvest.
The control board locks the ice machine in the freeze
cycle and a harvest cycle can not start for six minutes.
Maximum Freeze Time
The control system includes a built-in safety which will
automatically cycle the ice machine into harvest after
60 minutes in the freeze cycle.
Maximum Temperature
Maximum temperature for the ice thickness probe is
49 degree’s C. Do not clean probe in a dishwasher or
expose to temperatures above the maximum.