Fire damper - FDMQ
Page 92
Version 2023-07-27
TPM 103/14
FDMQ 800x400/375 - .40 A
EXAMPLE:
FDMQ 800x400/375 - .40 A
- 800x400-damper size, /375-building lenght of a damper, .40-damper design,
A-with protective cladding boards
building length of a damper
size AxB
design
■
If dampers with installation frame are required, that must be specified separately in the order. The installation frame can be installed on
the damper or delivered separately.
■
Detailed information for ATEX dampers (ZONE 1,2)
- without protective cladding boards
A
- with protective cladding boards
X. ORDERING INFORMATIONS
Ordering key
Fire damper
Damper design
Additional digit
Manual control and thermal
.01
Manual control and thermal (Zone 1,2)
.02
Manual control and thermal with a terminal switch („CLOSED“)
.11
Manual control and thermal with a terminal switch („CLOSED“) (Zone 1,2)
.12
Manual control and thermal with two terminal switches („OPEN“, „CLOSED“)
.80
Manual control and thermal with two terminal switches („OPEN“, „CLOSED“) (Zone 1,2)
.81
With actuator BF 230-TN (BFL, BFN 230-T) - voltage AC 230 V
.40
With actuator BF 24-TN (BFL, BFN 24-T), with smoke detector ORS 142 K and with supply device BKN 230-24-MOD
(voltage AC 230 V)
.41
With actuator ExMax-15-BF, with thermoelectric activation device ExPro-TT (Zone 1,2) - supply voltage range 24 to 230
VAC/DC
.42
With actuator BF 24-TN (BFL, BFN 24-T) - voltage AC/DC 24 V
.50
With actuator BF 24-TN (BFL, BFN 24-T), with smoke detector ORS 142 K (voltage AC/DC 24 V)
.51
With communication and supply device BKN 230-24 and actuator BF 24-TN-ST (BFL, BFN 24-T-ST)
.60
With communication and supply device BKN 230-24-C-MP, with actuator BF 24-TN-ST (BFL, BFN 24-T-ST)
.61
With communication and supply device BKN 230-24-C-MP, with actuator BF 24-TN-ST (BFL, BFN 24-T-ST) and with smoke
detector ORS 142 K
.61S
With communication and supply device BKN 230-24MP and with actuator BF 24TL-TN-ST (Top-Line) for connection to
MP-Bus
.62
With communication and supply device BKN 230-24-MOD, with actuator BF 24-TN-ST (BFL, BFN 24-T-ST)
.63
With communication and supply device BKN 230-24-MOD, with actuator BF 24-TN-ST (BFL, BFN 24-T-ST) and with smoke
detector ORS 142 K
.63S