Page 11
Version 2023-07-27
Fire damper - FDMQ
TPM 103/14
Design .41 and .51
■
Design .41 or .51 with actuator and smoke detector ORS
142 K. The voltage can be AC 230 V or 24 V DC. Design .41
with voltage AC 230 V is equipped with communication
and supply device BKN 230-24-MOD and with actuator BF
24-TN (BFL 24-T, BFN 24-T).
■
The smoke detector is activated when smoke spreads in
air duct system. Deactivation of the smoke detector alarm
status is provided by interruption of supply voltage for
min. 2s.
■
Signalisation of damper blade position "OPEN" and
"CLOSE" is provided by two microswitches.
Design .41 with actuator BF 24-TN (BFL, BFN 24-T), with smoke detector ORS 142 K and with supply device BKN 230-24-MOD
(voltage AC 230 V)
1
2
3
4
5
6
7
1
2
S2
S1
S3
S5
S4
S6
2
3
4
5
6
1
BAT
Tf
Tf
LED
Communication and supply device BKN 230-24-MOD
Nominal voltage
AC 230 V 50/60Hz
Power consumption
3 W (operating position)
Dimensioning
14 VA (including actuator)
Protection Class
II
Degree of protection
IP 40
Ambient temperature
Non-operating temperature
-20°C … +50°C
-40°C … +80°C
Connection - net
- motor
- terminal board
cable 0,9 m with EURO plug type 26
6-pole connector, 3-pole connector
screw terminals for cable 2x1,5 mm²
Design .51 with actuator BF 24-TN (BFL, BFN 24-T), with smoke detector ORS 142 K (voltage 24 V DC)
1
2
S2
S1
S3
S5
S4
S6
24 V DC
2
3
4
5
6
1
BAT
Tf
Tf
LED