Page 45
Version 2023-07-27
Fire damper - FDMQ
TPM 103/14
≥ 100
variable
4
0
..
.1
1
0
X
4
0
..
.1
1
0
≥
100
X
≥
5
0
EIS 90
≥ 400
≥ 100
6
0
1
2
0
B
m
in
.
B
+
8
0
m
a
x
.
B
+
2
2
0
min. A+80
max. A+220
≥
50
≤
3
0
0
2
5
25
≥
5
0
≤ 300
A
50
1
FDMQ
2
Gypsum wall construction
3
Mineral wool board - min. density 140 kg/m
3
(e.g. PROMAPYR-T150,
ROCKWOOL HARDROCK / STEPROCK HD)
4
Fire-resistant coating - th. 1 mm (e.g. PROMASTOP-I)
5
Fire-resistant board - min. th. 15 mm, min. density 870 kg/m
3
(e.g.
PROMATECT-H)
6
Screw 4x50 mm - screws must be fixed in the wall construction, use steel
anchors if necessary
7
8
Insulation board made of mineral wool, with a surface treatment of
aluminum foil - th. 60 mm, min. density 300 kg/m³ - (System ROCKWOOL
Conlit Ductrock 90)
9
Duct penetration insulation collar - th. 60 mm (System ROCKWOOL Conlit
Ductrock 90) - glued (pos. 12) and fixed with screws to the wall construction
10
Insulation collar of the damper and duct connection - th. 60 mm (System
ROCKWOOL Conlit Ductrock 90)
11
Standard air duct, made of galvanized sheet metal min. thickness 0,8 mm
12
ROCKWOOL Firepro glue - apply on the insulation and fix it to the fire
separation construction
13
Profile with threaded rod
Outside gypsum wall constrution - mineral wool ROCKWOOL - mineral wool with fire-resistant coating and fire-
resistant board
■
For connection of following duct
■
Minimum and maximum distance between the wall and fire damper is unlimited
■
When installing the insulation, follow the ROCKWOOL manufacturer's instructions
■
The damper and the duct must be suspended separately
■
The duct must be suspended on both sides of damper acc. to national rules
■
Duct between fire damper and fire separating construction must be suspended by using threaded rods and mounting profiles, or another mounting system
acc. to national standards
■
Load of the suspension system depends on weight of the fire damper and duct system
■
Max. distance between two suspension systems is 1500 mm
■
Duct at the point of penetration must be fixed to the fire separation structure
■
Following air-conditioning duct must be suspended or supported so that all load transfer from the following duct to the fire damper is absolutely excluded.
Adjacent duct must be suspended or supported, as required by the duct suppliers
■
If the threaded rod is located inside the duct insulation, distance between threaded rod and duct is max 30 mm
■
If the threaded rod is located outside the duct isolation, distance between threaded rod and isolation is max. 40 mm
■
If the damper is installed outside the fire separation construction and a damper side A ≥ 800 mm, VRM-Q reinforcement frame must be used