Fire damper - FDMQ
Page 72
Version 2023-07-27
TPM 103/14
EIS 90
Installation at a maximum distance of 80 mm from the ceiling
■
X = ceiling movement = 10 to 40 mm
■
Y = distance of frame from ceiling max. 80 mm
■
F = gap between frame (promaseal) and profile = 2 to 5 mm
Installation frame
W
[mm]
Z
[mm]
E5
B + 224 + X + Y
A + 208 + (2 x F)
* Width of the boards for frame E5 = 110 mm
≤ 625
2x Screw
CW-Profile
UW-Profile
Connection of the flexible ceiling
according to wall specifications
Ceiling
Z
W
X
+
Y
+
2
0
Y
X
UW-profile (screwed to the con-
nection of the flexible ceiling)
* Cement-lime boards filling -
min. density 450 kg/m³
Closed sides of profile
Apply intumescent sealant between
the ceiling and boards
(e.g. Hilti CP611A, Promaseal-AG)
■
Detailed instructions for installation E5 frame
■
For connection of following duct
■
Installation frame can be installed on the damper or delivered separately
Gypsum construction must be made in accordance with the specifications of the wall system manufacturer
Connection of the flexible ceiling
according to wall specifications
UW-profile (screwed to the
connection of the flexible
ceiling)
Gypsum boards
Insulation