47DV
P. 34 / 34
EM-9501-B Rev.6
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive
remedies, under this warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this
warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original
sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
ERROR MESSAGES
MAIN DISPLAY
Scaling error
Non-volatile memory error (reading)
Non-volatile memory error (writing)
Note: The meter recovers normal status following its startup sequence (except the power ON delay) when it is out of an error status.
*
1. If the unit does not recover its function after the initialization, repairing at the factory may be required.
Input signal is over range. Increase/decrease the input signal until it is back
within the measuring range.
While the error message is on the display, press Up button for 3 seconds or
more, go to the lockout setting mode and initialize the unit to its factory
default status.
*
1
Repair is needed if the display does not recover after the power is reset.
ERROR MESSAGE
WHAT TO DO
Internal data error
Repair is needed if the display does not recover after the power is reset.
A/D converter error
Confirm that there is no abnormality (such as shortcircuit) at the external
connection for the excitation supply terminal
Excitation supply error
CHARACTER SET
0 1 2
4
3
5 6 7
9
8
– A B
D
C
E F G
I
H
J K L
N
M
O P Q
S
R
T U V W X
Z
Y
Shift
Loop Test Output
Measuring Mode
-20000...100000
Set value
Setting Parameters
Hold down Alarm/ + Scale/ + Shift
button for
≥
5 seconds
Hold down Alarm/ or Scale/ button
for
≥
1 second
Loop Test Output Mode
*
1. Hold down Alarm/ or Scale/ button for
≥
1 second to return to the measuring mode while setting parameters.
PARAMETER
FUNCTION
DEFAULT
VALUE
MAIN DISPLAY
SUB DISPLAY
...
Loop test output
Scaling value for the loop test output
N/A
(display blinking)
*
1
Loop test output: Pressing [Shift] button switches the signal to increase or decrease, and then pressing [Up] button controls it toward
the desired output value.
Alarm trip functions according to the loop test output.
Note 1: The loop test output mode can be used only with the DC output option.
Note 2: Do not attempt to write via Modbus while in the loop test output mode. Cancel the latching output mode before the testing.
*
1. The specified decimal point position is applied to the loop test output value.
LOOP TEST OUTPUT MODE
■
FLOWCHART
■
PARAMETERS LIST
INFRARED COMMUNICATION MODE
Hold down Alarm/
+ Up button for 3 seconds or more to enter Infrared Communication Mode. ‘IRU’ is inidcated on the
display.